S-2.1, r. 6 - Regulation respecting industrial and commercial establishments

Full text
5.2.2. In case of failure of the power required for the lighting of exits during occupancy of the establishment, an emergency lighting system shall:
(a)  be provided for the lighting of exits, and the notices indicating exits, passageways, corridors and alleys leading directly to exits;
(b)  maintain in areas required in paragraph a a level of illumination of 50 lux for a period of at least half an hour at floor level; and
(c)  be inspected monthly.
R.R.Q., 1981, c. S-2.1, r. 9, s. 5.2.2.